Cooling Water Treatment With Ozone

Paper Title: Cooling Water Treatment With Ozone

Abstract

Cooling Water Treatment With Ozone

Small scale tests on an open recirculating cooling system with a cooling water flow of 10 m3/h conducted for a period of two years have shown that ozone could be a viable alternative to chlorine and other commonly used biocides. An average ozone dosage of .05 mg/L was applied continuously to the cooling water. Corrosion rates of copper alloy samples immersed in ozonized water were lower than the rates of samples in non-ozonized water. No corrosion was detected for the Cr-Ni steel alloys DIN 1.4306 and DIN 1.4404 as well as for titanium either in the presence or absence of ozone in water. This is ascribed to the formation of a thin protective layer in both cases.

A pilot plant has been set up at the EVS Heilbronn coal-fired power station in West Germany in order to confirm the results obtained on a small scale. The open recirculating cooling system has a cooling water flow of 1,000 m3/h and is fed by conditioned Neckar river water. An air-fed ozone generator is used to ozonize a 10% side stream of the cooling water. A bubble diffuser contactor is used to introduce ozone into the water and an air heater is operated to decompose excess ozone leaving the contactor. The plant can be run to yield either a constant ozone residual concentration in the water or a constant ozone dosage to the water leaving the contactor. All relevant data are registered continuously and the plan presently is operated automatically with a constant ozone dosage in the side stream. Corrosion experiments are performed using laboratory heat exchangers, and all physical, chemical, and microbiological data of the cooling water are acquired. The operation started February 1, 1989 and is scheduled to be terminated by the end of 1990.

Problem

Water cooling system are used in thermal power plants. The efficiency of these systems affects the efficiency of the thermal power plant. Problems in the cooling system can arise in the form of deposits, corrosion and biological growth within the system. Most of these cooling systems are treated using chlorine, which is known for its health risks and adverse biological effects.

Testing / Method

Diagram: Cooling Water Treatment With Ozone

A small scale test was performed utilizing the same water flow and scale. The first reactor was cooled using ozonated water. In the second reactor no ozone was injected in the system. Corrosion tests were performed on both systems over the course of two years.

Conclusion / Results

Cooling Water Treatment With Ozone

The small scale test demonstrated that a low concentration of .05 mg/L of ozone is effective in treating water cooling systems. The corrosion levels with the use of ozone were less or non existent. The encouraging results from the test lead to the construction and operation of a pilot plant treating 1,000 m3/h cooling water in a West German power plant.

Source

Cooling Water Treatment With Ozone, Asea Brown Boveri Corporate Research, CH-5405 Baden, Switzerland, R. Wellauer and M. Oldani

The above information is from http://www.OzoneSolutions.com and is copyrighted by Ozone Solutions Inc.
Jump To TopOzone Solutions Inc. | (712) 439-6880Jump To Top